Network Power Divisions
Select A Division
Control Concepts
Emerson
Emerson Network Power
Liebert
Liebert Global Services
Printable Page
IL Series
Branch/Distribution
EDCO AC Power Transient Voltage Surge Suppressor,
an electronic grade surge protective device designed to protect electronic equipment and microprocessor-based systems from transients on sub-distribution panels, branch panels, or similar locations.
AC Power TVSS Technical Specification
Operating Voltage Range
+/15%
Fault Current Rating (AIC)
14 kAIC
Dimensions
4.72"x4.72"x2.36"
Operating Frequency Range
4763 Hz
Capacity
Continuous
50 Ohm EMI/RFI Attenuation
40 dB
Response Time
<0.5 ns
Operating Humidity
0% to 95%
Status Indication
LED, Dry Contacts
Certifications
UL 1449, CUL
Warranty
5 Years
UL 1449 (Second Edition) Classification
120 volt systems
400 volts all modes
208 and 277 volt systems
800 volts all modes
480 volt systems
1,500 volts all modes
ORDERING INFORMATION
Building A Model Number: IL 1 2 3
1: Nominal Voltage Requirements
2: System Configuration
3: Surge Current Capacity
Nominal Voltage
Requirements
Model ID
L-N
L-L
L-G
120
N/A
120
120
120
208
120
120
120
240
120
120
N/A
208
208
208
N/A
240
240
240
277
480
277
277
N/A
480
480
480
System Configuration
Model ID
Single (2-Wire + Gnd)
N or L
Split (3-Wire + Gnd)
S
Wye (4-Wire + Gnd)
Y
Delta Hi-Leg (4-Wire + Gnd)
H
Delta (3-Wire + Gnd)
D
Surge Current Capacity
Model ID
100 kA/Phase
100
(L-N: 50 + L-G: 50kA)
50 kA/Phase
50
(L-N: 25 kA + L-G: 25 kA; N-G: 25 kA)
25 kA/Phase
25-2