The DRS Series is a din-rail mountable,
single-pair surge suppression module implementing three-stage hybrid
technology. This module addresses overvoltage transients with gas
tubes and silicon avalanche components. In addition, sneak currents
are mitigated with ressetable fuses (PTCs). The PTCs increase resistance
several orders of magnitude when overcurrents exceed safe levels.
A normal state resumes when overcurrents are removed. The ability
to self-restore in this manner significantly increases suppressor
performance and survivability.
The DRS Series mounts onto a standard
35mm industrial din rail. There are three "Field Side" and
three "Electronics Side" screw terminals. One is reserved
for a shield. Three electrically tied ground terminals are provided
for grounding the DRS Series unit to Building Approved Ground. Shield
is isolated from ground. For a 2-terminal version without a shield
order the DRS-xxx-2.
FEATURES
• Low-Voltage
Data Surge Protection
• Three-Stage
Hybrid Protection
• Sneak/Fault
Current Protection With Resettable Fuses (PTCs)
• Low-Profile
Packaging
• Easy
Installation
• Fits
Standard 35mm Din Rail
• Fast Response
Time <1 Nanosecond
• UL 497B
Listed
SPECIFICATIONS
Part #
Max Peak Signal Voltage
Nominal Breakdown Voltage
Max Current Ip 10X1000µs (Occurrences)
Peak Current 8x20µs
Typ Cap (pf)
Max Continuous Current
Nominal Series Resistance
DRS-008
6
8
>100
10KA
1500
150ma
5 Ohms
DRS-015
12
15
>100
10KA
1500
150ma
5 Ohms
DRS-232
15
22
>100
10KA
1500
150ma
5 Ohms
DRS-030
24
30
>100
10KA
1500
150ma
5 Ohms
DRS-036
30
36
>100
10KA
1500
150ma
5 Ohms
DRS-043
35
43
>100
10KA
1500
150ma
5 Ohms
DRS-050
43
50
>100
10KA
1500
150ma
5 Ohms
DRS-060
52
60
>100
10KA
1500
150ma
5 Ohms
DRS-175
200
250
>10
8KA
1500
150ma
5 Ohms
** DRS-130 RMS
170
200
>10
8KA
1500
5000
None
** WARNING!!For Discrete Signal Use Only.
Do not use DRS-130RMS
on 120 VAC Power Lines. This unit is a Non-Hybrid, MOV
design, rated above 5A operational current and can withstand
greater than eight occurrences of a 10kA 8x20µs
waveform, and greater than 1000 occurrences of a 200A
10x1000µs waveform.