FAS-1 and FAS-2 Series
Camera Power Line Post-Indicator Valve Circuit Bell, Horn, Strobe Circuit
The FAS-1 and FAS-2 Series is a multi-stage single- or two-pair surge suppressor designed for high-exposure applications. These products were specifically designed to meet multiple low-voltage protection applications in the fire and security industry.
| FEATURES |
| • Lightning Protection for Low-Voltage Data/Signal Lines |
| • Multi-Stage Protection |
| • Common Mode and Differential Protection Mode |
| • Automatic Recovery |
| • Fast Response Time |
| • UL 497B Listed |
|
 |
|
| SPECIFICATIONS |
| Peak Surge Current (10 Times): |
| 8 x 20µs |
10kA (2500A per line) |
| 10 x 700µs |
500A per line |
| Life Expectancy: |
| 8 x 20µs (2000A) |
100X |
| 10 x 700µs (400A) |
100X |
| Response Time |
1ns |
| Clamping Voltage |
18, 33, 43 or 60V |
| Technology |
SAD Hybrid |
| Series Resistance |
0.2 Ohms/pr. |
| Capacitance (average) |
1500pf |
| Operating Temperature |
–40°C to +85°C |
| Weight |
4 oz. |
| Dimensions (inches): H x W x L |
| (–1) |
2.0 in. x 1.5 in. x 1.0 in. |
| (–2) |
2.0 in. x 2.0 in. x 1.5 in. |
|
|
 |
| ORDERING INFORMATION |
| 12VDC use: |
FAS-1-018HC (single pair)
FAS-2-018HC (two pair) |
| 24VDC use: |
FAS-1-033HC (single pair)
FAS-2-033HC (two pair) |
| 24VAC use: |
FAS-1-043HC (single pair)
FAS-2-043HC (two pair) |
| 48V Systems use: |
*FAS-1-060HC (single pair) *FAS-2-060HC (two pair) |
*THESE MODELS NOT UL LISTED
Caution: The hybrid design of this product includes series resistance. Do not place this product in service on any signal line capable of supplying more than 2.5 Amperes continuously. |
|

|
 |
 |
|