# #2017 Protecting School Intercom Systems

THE PURPOSE OF THIS BULLETIN IS TO ASSIST
USERS/INSTALLERS TO ACCOMPLISH THE FOLLOWING
Select the correct suppressors for the application (i.e., inside building, outside building lines).
Proper suppressor system installation and wiring.
Assurance of adequate grounding practice.

COMMENTS ON FIGURE 1
1. Bridging clips will be required on TBLK when using the OPX Series Suppressors.
2. Cable bundles to classrooms must be kept separate from cable bundles to equipment cabinet.
3. Cable bundles to classrooms must terminate on ground rail side of TBLK.
4. The TBLK can accommodate up to 25 suppressors (any combination of the above example part numbers).
5. For more detail on proper grounding, refer to Tech Bulletin #1090.
6. For best results, protect all conductors entering or leaving equipment cabinet.
7. Multiple TBLK's can be mounted in termination cabinet.
8. COHP-50 can be used up to a total load of 7 Watts per pair. For loads above 7 Watts, refer to the PHC Series Data Sheet.
Standard Wiring Use TBLK Assembly
COMMENTS ON FIGURE 2
1. Bridging clips will be required on M1-50 when using the OPX Series Suppressors.
2. Cable bundles to classrooms must be kept separate from cable bundles to equipment cabinet.
3. Cable bundles to classrooms must terminate on ground rail side of M1-50.
4. The M1-50 can accommodate up to 25 suppressors (any combination of the above example part numbers).
5. For more detail on proper grounding, refer to Tech Bulletin #1090.
6. For best results, protect all conductors entering or leaving equipment cabinet.
7. Multiple M1-50 blocks can be mounted in termination cabinet.
8. COHP-50 can be used up to a total load of 7 Watts per pair. For loads above 7 Watts, refer to the PHC Series Data Sheet.
Solid 22 GA Wiring Use M1-50 Punchdown Block